The digital outputs support both PNP and NPN types of wirings. You can find detailed
information from the following diagrams:
NPN wiring PNP wiring
DIs/Dos for SINAMICS V90 PTI
DIs
You can assign a maximum of 28 internal digital input signals to the SINAMICS V90 servo
drive. For detailed information about these signals, see the table below:
1 SON Edge
0→1
1→0
Servo-on
• 0→1: powers on power circuit and makes servo
drive ready to operate.
• 1→0: motor ramps down (OFF1) in PTI, IPos, and
S modes; motor coasts down (OFF2) in T mode.
✓ ✓ ✓ ✓
2 RESET Edge
0→1
Reset alarms
• 0→1: Reset alarms
✓ ✓ ✓ ✓
3 CWL Edge
1→0
Clockwise over-travel limit (positive limit)
• 1 = condition for operation
• 1→0: emergency stop (OFF3)
✓ ✓ ✓ ✓
4 CCWL Edge
1→0
Counter-clockwise over-travel limit (negative limit)
• 1 = condition for operation
• 1→0: emergency stop (OFF3)
✓ ✓ ✓ ✓
5 G-
CHANGE
Level Gain change between the first and the second gain
parameter set.
• 0: the first gain parameter set
• 1: the second gain parameter set