Procedure
In non-flameproof enclosure In flameproof enclosure Ex d
1. Adjust the working area to your application by turning the
adjustment wheel of the friction clutch .
2. Fasten the friction clutch. Insert a standard approx. 4 mm
wide screwdriver in the friction clutch gear latch .
3. Use the screwdriver to turn the friction clutch gear
latch counterclockwise until it engages. The friction
clutch is locked.
1. Adjust the working range by slightly turning the adjust‐
ment wheel of the friction clutch over the hole with a
pin.
CAUTION
Follow the steps below to avoid damage to your device.
The friction clutch is outside the flameproof enclosure
at the bottom.
Do not loosen the screws on the adjustment wheel of the
friction clutch .
Frequent twisting of the friction clutch is not provided for
due to the design.
It is not necessary to lock the friction clutch.
Commissioning
7.8 Setting the friction clutch
SIPART PS2 with 4 to 20 mA/HART
116 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
TypeElectropneumatic
Input Signal4-20 mA
Stroke Range3 to 200 mm
Rotary Range30 to 100°
MountingLinear or rotary actuators
CertificationsATEX, IECEx, FM, CSA