11.2.4.11 Diagnostic value '13.PRPST' - Time since last partial stroke test'
Indication on the display: ###
notSt
Sdtst
FdtSt
Purpose: This diagnostics parameter shows the elapsed time in days since
the last partial stroke test.
Status messages: notSt - No Test: A manual partial stroke test has not yet been
executed.
SdtSt - Stopped Test: The last partial stroke test was interrupted.
FdtSt - Failed Test: The last partial stroke test has failed.
11.2.4.12 Diagnostic value '13.PRPST - Time since last partial stroke test' (version with pressure
sensor module)
Indication on the display: ###
notSt
noREF
Sdtst
FdtSt
Purpose: This diagnostics parameter shows the elapsed time in days since
the last partial stroke test.
Status messages: notSt - No Test: A manual partial stroke test has not yet been
executed.
noREF: A reference partial stroke test has not yet been execu‐
ted.
SdtSt - Stopped Test: The last partial stroke test was interrupted.
FdtSt - Failed Test: The last partial stroke test has failed.
11.2.4.13 Diagnostic value '14.NXPST - Time until next partial stroke test'
Requirement: The partial stroke test is activated in 'Configuration' mode.
The test interval is set in the 'A8.INTRV' parameter.
Indication on the display: OFF
###
Purpose: This diagnostics parameter shows the time in days until the next
partial stroke test. If one of the above-mentioned conditions is not
met, 'OFF' is shown on the display.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 219

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
TypeElectropneumatic
Input Signal4-20 mA
Stroke Range3 to 200 mm
Rotary Range30 to 100°
MountingLinear or rotary actuators
CertificationsATEX, IECEx, FM, CSA