EasyManuals Logo

Siemens SIPART PS2 series User Manual

Siemens SIPART PS2 series
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
14.Close the positioner as described in Closing the standard and and intrinsically safe version
(Page 53).
15.Set the limits L1 and L2 as described in Setting limits (Page 64).
4.5.4.3 Setting limits
Procedure: Determining the switch status of the slotted initiators
You will require a suitable display device to determine the switch status. For example, use the
initiator tester type 2 / Ex from Pepperl + Fuchs.
1. Connect the display device to the following terminals of the Inductive Limit Switches (ILS):
41 and 42
51 and 52
2. Read the switch status of slotted initiators.
Procedure: Setting the limits L1 and L2
The consecutive numbers in the following text refer to the figure above in this section. Proceed
as follows to set the limits:
1. Move the actuator to the first desired mechanical position.
2. Adjust the upper actuating disk manually until the output signal at terminals 41 and 42
changes. Set a high-low or a low-high switchover as follows:
Rotate the actuating disc beyond the switching point until you reach the next
switching point.
3. Move the actuator to the second desired mechanical position.
4. Adjust the lower actuating disk manually until the output signal at terminals 51 and 52
changes. Set a high-low or a low-high switchover as follows:
Rotate the actuating disc beyond the switching point until you reach the next
switching point.
Note
Adjusting the actuating disk
The actuating disks and are relatively difficult to move. This design prevents their
unintentional movement during operation. You can achieve an easier and finer
adjustment by reducing stiction temporarily.
Move the actuator to and fro while simultaneously holding the actuating disks
and .
Installing/mounting
4.5 Installing option modules
SIPART PS2 with 4 to 20 mA/HART
64 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Enclosure RatingIP66/NEMA 4X
TypeElectropneumatic
Input Signal4-20 mA
Stroke Range3 to 200 mm
Rotary Range30 to 100°
MountingLinear or rotary actuators
CertificationsATEX, IECEx, FM, CSA