Message Line Meaning/cause Measure
Up Down
nn.n X Initialization completed successfully with the
display of actuator travel or the actuator angle
1. Briefly acknowledge using button.
2. Leave configuration level with a long
press on the button.
FINISH X
See also
System messages before initialization (Page 207)
11.1.3 System messages when exiting the Configuration mode
Remarks about the tables:
nn Stands for variable numeric values
Error symbol
/ (slash): the texts on the left and right of the slash flash alternately
Messages when exiting the configuration mode:
Message Line Operating mode Meaning / cause Measure
Up Bot‐
tom
Automatic Manual mode P manual mode
n.nn.nn-
nn
X
X
Software version
Maintenance
Error
SLnn
X
X
Monotony interruption
of the free character‐
istic on the setpoint
turning point n
Correct the value
11.1.4 System messages during operation
Remarks about the tables:
nn Stands for variable numeric values
Error symbol
/ (slash): The texts on the left and right of the slash flash alternately
Diagnostics and troubleshooting
11.1 Output of system messages in the display
SIPART PS2 with 4 to 20 mA/HART
210 Operating Instructions, 11/2019, A5E00074631-AE