To optimize the sensitivity of the monitoring of the pneumatic leak‐
age to your specific application, follow these steps:
1. After initializing the positioner automatically, use a calibration
device to initiate a ramp movement.
2. Conditions for the ramp movement:
The ramp covers the normal operating range of the valve.
The steepness of the ramp matches the dynamic require‐
ments of the corresponding application.
The characteristic of the ramp corresponds to the character‐
istic of the setpoint that actually occurs.
3. During the ramp movement, the Diagnostic value '16.ONLK -
Pneumatic leakage' (Page 220) provides information about the
actual values. Define the limit of the leakage indicator accord‐
ingly.
The positioner triggers a message if the current value exceeds one
of the three thresholds. How to set the three thresholds is described
below.
Factory setting: 30.0
C2.FACT1 - Factor 1
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'C1.LIMIT' and 'C2.FACT1'.
A leakage was detected when threshold 1 is exceeded. The control
quality is not affected. The threshold 1 message is shown. This
message is only output if threshold 2 or 3 is not exceeded at the
same time.
The process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 1.0
C3.FACT2 - Factor 2
Adjustment range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 2.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'C1.LIMIT' and 'C3.FACT2'.
A leakage was detected when threshold 2 is exceeded. The control
quality is affected. Maintenance is recommended. The threshold 2
message is shown. This message is only output if threshold 3 is not
exceeded at the same time.
The process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 1.5
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
172 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals