d1.LIMIT - limit for slipstick detection
Setting range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the base limit for slipstick detection in
percent. Set the base limit in a range from '0.1' to '100.0'.
Factory setting: 1.0
d2.FACT1 - Factor 1
Setting range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd2.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. This message is only output if threshold 2 or 3 is not exceeded
at the same time. The process to activate and display this message
is described in the 'XDIAG' parameter.
Factory setting: 2.0
d3.FACT2 - Factor 2
Setting range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 2.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd3.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. This message is only output if threshold 3 is not exceeded at
the same time. The process to activate and display this message is
described in the 'XDIAG' parameter.
Factory setting: 5.0
d4.FACT3 - Factor 3
Setting range: 0.1 ... 100.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 3.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd4.FACT3'.
The threshold 3 message is displayed when threshold 3 is excee‐
ded. The process to activate and display this message is described
in the 'XDIAG' parameter.
Factory setting: 10.0
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
174 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals