Table 2-12 Measured values constellation for device 1
No. Information Type of
Information
Comments
7761
Relay ID
MV Device address of the device
7762
I A_opN=
MV
ΙA (% of nominal operational current)
7763
ΦI A=
MV
Winkel ΙA_remote <-> ΙA_local
7764
I B_opN=
MV
ΙB (% of nominal operational current)
7765
ΦI B=
MV
Angle ΙB_remote <-> ΙB_local
7766
I C_opN=
MW
ΙC (% of nominal operational current)
7767
ΦI C=
MV
Angle ΙC_remote <-> ΙC_local
7769
V A_opN=
MV VA (% of nominal operational voltage)
7770
ΦV A=
MV Angle VA_remote <-> VA_local
7771
V B_opN=
MV VB (% of nominal operational voltage)
7772
ΦV C=
MV Angle VB_remote <-> VB_local
7773
V C_opN=
MV VC (% of nominal operational voltage)
7774
ΦV C=
MV Angle VC_remote <-> VC_local
Min/Max Measurement Setup
Minimum and maximum values are calculated by the 7SD80. Time and date of the last update of the values
can also be read out.
Functional Description
Minimum and Maximum Values
The minimum and maximum values for the three phase currents Ι
x
, the three phase voltages V
x-N
, the phaseto-
phase voltages V
xy
, the positive sequence component Ι
1
and V
1
, the active power P, reactive power Q, and
apparent power S, the frequency, and the power factor cos φ a formed as primary values including the date
and time they were last updated.
The minimum and maximum values of the long-term mean values listed in the next section are also calcu-
lated.
The minimum and maximum values can be reset at any time via binary inputs or by using the integrated
control panel or the DIGSI software. Additionally, the reset can be carried out cyclically, starting at a preset
point of time.
Setting Notes
Minimum and Maximum Values
The minimum and maximum values can be reset automatically at a programmable point in time. This feature
can be activated by setting address 2811 MinMax cycRESET to YES.
At address 2812 MiMa RESET TIME you can define the point of time when resetting takes place (minute of
the day).
Address 2813 MiMa RESETCYCLE allows you to define the resetting cycle (in days).
At address 2814 MinMaxRES.START you can define when the cyclic process of forming the minimum and
maximum values begins (in days, counted from the time of parameterization).
Settings
Addr.
Parameter Setting Options Default Setting Comments
2811 MinMax cycRESET NO
YES
YES Automatic Cyclic Reset Function
2.17.6
2.17.6.1
2.17.6.2
2.17.6.3
Functions
2.17 Auxiliary Functions
SIPROTEC 4, 7SD80, Manual 187
E50417-G1100-C474-A2, Edition 02.2018

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7SD80 and is the answer not in the manual?

Siemens SIPROTEC 4 7SD80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7SD80
CategoryPower distribution unit
LanguageEnglish

Related product manuals