Characteristics
General Properties
Powerful 32-bit microprocessor system
Complete digital processing of measured values and control, from the sampling of the analog input
values, the processing and organization of the communication between devices up to the closing and
tripping commands to the circuit breakers.
Total galvanic and fail-safe separation of the internal processing circuits from the measuring, control and
supply circuits of the system via measuring transformers, binary input and output modules and DC or AC
converters
Suited for lines with two ends
Easy device operation using the integrated operator panel or from a connected personal computer
running DIGSI
Storage of fault indications as well as instantaneous values for fault recording
Digital protection data transmission; communication of the device through optical fiber cables
Communication is possible via a single copper wire pair (typically 8 km (4.97 miles), max. 20 km (12.43
miles), depending on the used cable type, see Section 4 Technical Data).
Permanent supervision of the protection data transmission for disturbance, failure or transfer time varia-
tions
Phase Comparison Protection
Differential protection for two ends with digital protection data transmission
Protection for all types of short-circuits in systems with any starpoint conditioning
Reliable distinction between load and short-circuit conditions using adaptive measurement methods, also
for high-resistance faults with small fault currents
High sensitivity in light load operation, highest stability against load steps and power fluctuations
Due to phase segregated measurement, the pickup sensitivity is independent of the fault type
Detection of high-resistance, weak-current faults due to high sensitivity of the protection functions
Fast tripping also on weak or zero infeed ends (breaker intertrip)
No frequency dependency
Ground Fault Differential Protection for Grounded Systems
Short command time
High sensitivity for short circuits to ground
High stability against external ground faults by stabilizing the through-flowing ground current
Ground Fault Differential Protection for Isolated / Grounded Systems
Short command time
High sensitivity for short circuits to ground
High stability against external short-circuits to ground using the magnitude and phase relationship of the
ground current flowing through for stabilization
External Direct and Remote Tripping
Tripping of the local end by an external device via binary input
Tripping of the opposite end by local protection functions or by an external device via binary input