No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
561 Manual close signal
detected
(Man.Clos.Detect)
P.System
Data 2
OUT O
N
* * LED BO 15
0
21
1
1 No
563 CB alarm suppressed (CB
Alarm Supp)
P.System
Data 2
OUT * * * LED BO
590 Line closure detected
(Line closure)
P.System
Data 2
OUT * On
Off
* LED BO
916 Increment of active
energy (WpΔ=)
Energy -
917 Increment of reactive
energy (WqΔ=)
Energy -
1000 Number of breaker TRIP
commands (# TRIPs=)
Statistics VI
1027 Accumulation of inter-
rupted current Ph A (Σ Ia
=)
Statistics VI
1028 Accumulation of inter-
rupted current Ph B (Σ Ib
=)
Statistics VI
1029 Accumulation of inter-
rupted current Ph C (Σ Ic
=)
Statistics VI
1030 max. fault current Phase
A (Ia max. =)
Statistics VI
1031 max. fault current Phase
B (Ib max. =)
Statistics VI
1032 max. fault current Phase
C (Ic max. =)
Statistics VI
1401 >50BF: Switch on breaker
fail prot. (>50BF on)
50BF BkrFai-
lure
SP * * * LED BI BO
1402 >50BF: Switch off breaker
fail prot. (>50BF off)
50BF BkrFai-
lure
SP * * * LED BI BO
1403 >BLOCK 50BF (>BLOCK
50BF)
50BF BkrFai-
lure
SP O
N
OF
F
* * LED BI BO 16
6
10
3
1 Yes
1404 >50BF use 3I0 threshold
(>50BF 3I0>)
50BF BkrFai-
lure
SP O
N
OF
F
* * LED BI BO
1415 >50BF: External start
3pole (>50BF Start 3p)
50BF BkrFai-
lure
SP O
N
OF
F
* * LED BI BO
Functions, Settings, Information
F.3 Information List
366 SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018