2.10 Automatic Reclosure Function (optional)
145
7SD610 Manual
C53000-G1176-C145-4
For the 3rd cycle:
For the 4th cycle:
5th to 8th reclosure
cycle
If more than four cycles were set during configuration of the functional scope, the dead
times preceding the fifth (5th) through the ninth (9th) reclosing attempts are equal to
the open breaker time which precedes the fourth (4th) reclosing attempt.
Notes on the Infor-
mation Overview
The most important information about automatic reclosure is briefly explained insofar
as it was not mentioned in the following lists or described in detail in the preceding text.
„>BLK 1.AR-cycle“ (No. 2742) to „>BLK 4.-n. AR“ (No. 2745)
The respective auto-reclose cycle is blocked. If the blocking state already exists when
the automatic reclosure function is initiated, the blocked cycle is not executed and may
be skipped (if other cycles are permitted). The same applies if the automatic reclosure
function is started (running), but not internally blocked. If the block signal of a cycle
appears while this cycle is being executed (in progress), the automatic reclosure func-
tion is blocked dynamically; no further automatic reclosures cycles are then executed.
„AR 1.CycZoneRel“ (No. 2889) to „AR 4.CycZoneRel“ (No. 2892)
3468 2.AR Tdead3Trip Dead time after three-pole tripping
3469 2.AR: Tdead EV. Dead time after evolving fault
3470 2.AR: CB? CLOSE CB ready interrogation before reclosing
3471 2.AR SynRequest Sync. check after three-pole tripping
3472 3.AR: START Start in 3rd cycle generally allowed
3473 3.AR: T-ACTION Action time for the 3rd cycle
3475 3.AR Tdead 1Flt Dead time after single-phase pickup
3476 3.AR Tdead 2Flt Dead time after two-phase pickup
3477 3.AR Tdead 3Flt Dead time after three-phase pickup
3478 3.AR Tdead1Trip Dead time after single-pole tripping
3479 3.AR Tdead3Trip Dead time after three-pole tripping
3480 3.AR: Tdead EV. Dead time after evolving fault
3481 3.AR: CB? CLOSE CB ready interrogation before reclosing
3482 3.AR SynRequest Sync. check after three-pole tripping
3483 4.AR: START Start in 4th cycle generally allowed
3484 4.AR: T-ACTION Action time for the 4th cycle
3486 4.AR Tdead 1Flt Dead time after single-phase pickup
3487 4.AR Tdead 2Flt Dead time after two-phase pickup
3488 4.AR Tdead 3Flt Dead time after three-phase pickup
3489 4.AR Tdead1Trip Dead time after single-pole tripping
3490 4.AR Tdead3Trip Dead time after three-pole tripping
3491 4.AR: Tdead EV. Dead time after evolving fault
3492 4.AR: CB? CLOSE CB ready interrogation before reclosing
3493 4.AR SynRequest Sync. check after three-pole tripping