2 Functions
256
7SD610 Manual
C53000-G1176-C145-4
2.18 Command Processing
The SIPROTEC 4 7SD610 includes a command editing for initiating switching opera-
tions in the system. Control can originate from four command sources:
• Local operation using the keypad on the local user interface of the device,
• Operation using DIGSI,
• Remote operation using a substation automation and control system (e.g. SICAM),
• Automatic functions (e.g. using binary inputs, CFC).
The number of switchgear devices that can be controlled is solely limited by the
number of available and required binary inputs and outputs. For the output of control
commands it has to be ensured that all the required binary inputs and outputs are con-
figured and provided with the correct properties.
If specific interlocking conditions are needed for the execution of commands, the user
can program the device with bay interlocking by means of the user-defined logic func-
tions (CFC). The interlocking conditions of the system can be injected via the system
interface and must be allocated accordingly.
The procedure for switching resources is described in the SIPROTEC 4 System De-
scription under Control of Switchgear.
2.18.1 Control Authorization
2.18.1.1 Type of Commands
Commands to the
Process
This type of commands are directly output to the switchgear to change their process
state:
• Commands for the operation of circuit breakers as well as commands for the control
of isolators and earthing disconnectors,
• Step commands, e.g. for raising and lowering transformer taps,
• Setpoint commands with configurable time settings, e.g. to control Petersen coils.
Device-internal
Commands
These commands do not directly operate binary outputs. They serve for initiating in-
ternal functions, communicating the detection of status changes to the device or for
acknowledging them.
• Manual override commands for „manual update“ of information on process-depen-
dent objects such as annunciations and switching states, e.g. if the communication
with the process is interrupted. Manually overidden objects are marked as such in
the information status and can be displayed accordingly.
• Flagging commands (for „setting“) the data value of internal objects, e.g. switching
authority (remote/local), parameter switchovers, transmission blockages and dele-
tion and presetting of metered values.
• Acknowledgment and resetting commands for setting and resetting internal buffers
or data stocks.
• Information status commands to set/delete the additional „Information Status“ item
of a process object, such as
– Acquisition blocking,
– Output blocking.
www . ElectricalPartManuals . com