2 Functions
120
7SD610 Manual
C53000-G1176-C145-4
2.9.5 Information List
2694 3I0p Dir. 1A 0.05 .. 4.00 A; ∞∞A 3I0p directional Pickup
5A 0.25 .. 20.00 A; ∞∞A
2695 T 3I0p Dir. 0.05 .. 3.00 sec; ∞ 0.50 sec T 3I0p Dir.:Inv.-Time delay
for IEC-Char
2696 D 3I0p Dir. 0.50 .. 15.00 ; ∞ 5.00 D 3I0p Dir.:Inv.-Time delay
for ANSI-Ch.
2697 T 3I0p Add Dir. 0.00 .. 30.00 sec 0.00 sec T 3I0p Dir.: additional time
delay
2698 IPDir.Telep/BI NO
YES
NO Instantaneous trip via Tele-
prot./BI
2699 IP Dir. SOTF NO
YES
NO Instantaneous trip after
SwitchOnToFault
No. Information Type of In-
formation
Comments
7104 >BLOCK O/C I>> SP >BLOCK Backup OverCurrent I>>
7105 >BLOCK O/C I> SP >BLOCK Backup OverCurrent I>
7106 >BLOCK O/C Ip SP >BLOCK Backup OverCurrent Ip
7107 >BLOCK O/C Ie>> SP >BLOCK Backup OverCurrent Ie>>
7108 >BLOCK O/C Ie> SP >BLOCK Backup OverCurrent Ie>
7109 >BLOCK O/C Iep SP >BLOCK Backup OverCurrent Iep
7110 >O/C InstTRIP SP >Backup OverCurrent InstantaneousTrip
7111 >BLOCK Dir. I> SP >BLOCK direct. Backup OverCurrent I>
7112 >BLOCK Dir. Ip SP >BLOCK direct. Backup OverCurrent Ip
7113 >BLOCK Dir. Ie> SP >BLOCK direct. Backup OverCurrent Ie>
7114 >BLOCK Dir. Iep SP >BLOCK direct. Backup OverCurrent Iep
7130 >BLOCK I-STUB SP >BLOCK I-STUB
7131 >I-STUB ENABLE SP >Enable I-STUB-Bus function
7132 >BLOCK O/CIe>>> SP >BLOCK Backup OverCurrent Ie>>>
7151 O/C OFF OUT Backup O/C is switched OFF
7152 O/C BLOCK OUT Backup O/C is BLOCKED
7153 O/C ACTIVE OUT Backup O/C is ACTIVE
7161 O/C PICKUP OUT Backup O/C PICKED UP
7162 O/C Pickup L1 OUT Backup O/C PICKUP L1
7163 O/C Pickup L2 OUT Backup O/C PICKUP L2
7164 O/C Pickup L3 OUT Backup O/C PICKUP L3
7165 O/C Pickup E OUT Backup O/C PICKUP EARTH
7171 O/C PU only E OUT Backup O/C Pickup - Only EARTH
7172 O/C PU 1p. L1 OUT Backup O/C Pickup - Only L1
7173 O/C Pickup L1E OUT Backup O/C Pickup L1E
7174 O/C PU 1p. L2 OUT Backup O/C Pickup - Only L2
7175 O/C Pickup L2E OUT Backup O/C Pickup L2E
7176 O/C Pickup L12 OUT Backup O/C Pickup L12
Addr. Parameter C Setting Options Default Setting Comments