EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Technical Data

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.1 General
321
7SD610 Manual
C53000-G1176-C145-4
4.1.2 Auxiliary voltage
Direct Voltage
AC Voltage
1)
Max. permissible ambient temperature +55 °C when operated with 230 V~
Voltage supply via integrated AC/DC converter
Nominal auxiliary voltage U
H
– 24/48 VDC 60/110/125 VDC 110/125/220/250 VD
C
Admissible voltage ranges 19 to 58 VDC 48 to 150 VDC 88 to 300 VDC
Superimposed AC ripple voltage,
Peak to peak IEC60255–11
≤ 15 % of the nominal auxiliary voltage
Power Input
- Quiescent Approx. 6.5 W
- Energized Approx. 10 W
Plus approx. 1.5 W per interface module
Bridging time for failure / short circuit of DC auxiliary
voltage
≥ 50 ms at U
Aux
= 48 V and U
Aux
≥110 V
≥ 20 ms at U
Aux
= 24 V and U
Aux
≥60 V
Voltage supply via integrated AC/DC converter
Nominal Auxiliary Voltage AC U
Aux
230 V~
(release /CC and higher)
1)
115/230 V~
Admissible voltage ranges
184 to 265 V~
92 to 265 V~
Power Input
- Quiescent Approx. 10 VA
- Energized Approx. 17 VA
Plus approx. 1.5 VA per interface module
Bridging time for failure/short circuit of alternating
auxiliary voltage
≥ 50 ms
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals