2 Functions
214
7SD610 Manual
C53000-G1176-C145-4
2.15.1.8 Information List
2906A ΣI THRESHOLD 1A 0.10 .. 2.00 A 0.25 A Summated Current Moni-
toring Threshold
5A 0.50 .. 10.00 A 1.25 A
2907A ΣI FACTOR 0.00 .. 0.95 0.50 Summated Current Moni-
toring Factor
2908A T BAL. U LIMIT 5 .. 100 sec 5 sec T Balance Factor for
Voltage Monitor
2909A T BAL. I LIMIT 5 .. 100 sec 5 sec T Current Balance Monitor
2910 FUSE FAIL MON. ON
OFF
ON Fuse Failure Monitor
2911A FFM U>(min) 10 .. 100 V 30 V Minimum Voltage Thresh-
old U>
2912A FFM I< (max) 1A 0.10 .. 1.00 A 0.10 A Maximum Current Thresh-
old I<
5A 0.50 .. 5.00 A 0.50 A
2913A FFM U<max (3ph) 2 .. 100 V 5 V Maximum Voltage Thresh-
old U< (3phase)
2914A FFM Idelta (3p) 1A 0.05 .. 1.00 A 0.10 A Delta Current Threshold
(3phase)
5A 0.25 .. 5.00 A 0.50 A
2915 V-Supervision w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP Voltage Failure Supervi-
sion
2916A T V-Supervision 0.00 .. 30.00 sec 3.00 sec Delay Voltage Failure Su-
pervision
2921 T mcb 0 .. 30 ms 0 ms VT mcb operating time
2931 BROKEN WIRE ON
OFF
OFF Fast broken current-wire
supervision
2933 FAST Σ i SUPERV ON
OFF
ON State of fast current sum-
mation supervis
2941 ϕA 0 .. 359 ° 200 ° Limit setting PhiA
2942 ϕB 0 .. 359 ° 340 ° Limit setting PhiB
2943 I1> 1A 0.05 .. 2.00 A 0.05 A Minimum value I1>
5A 0.25 .. 10.00 A 0.25 A
2944 U1> 2 .. 70 V 20 V Minimum value U1>
No. Information Type of In-
formation
Comments
130 Ï•(PQ Pos. Seq.) OUT Load angle Phi(PQ Positive sequence)
131 Ï•(PQ Pos) block OUT Load angle Phi(PQ) blocked
132 ϕ Set wrong OUT Setting error: |PhiA - PhiB| < 3°
161 Fail I Superv. OUT Failure: General Current Supervision
163 Fail I balance OUT Failure: Current Balance
164 Fail U Superv. OUT Failure: General Voltage Supervision
Addr. Parameter C Setting Options Default Setting Comments