EasyManua.ls Logo

Siemens SIPROTEC 7SD610 - Page 155

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.11 Undervoltage and Overvoltage Protection (optional)
155
7SD610 Manual
C53000-G1176-C145-4
Figure 2-56 Logic diagram of the overvoltage protection for the negative sequence voltage system U
2
The overvoltage protection for the negative sequence system can also be blocked via
a binary input „>U2>(>) BLK“. The stages of the negative sequence voltage protec-
tion are automatically blocked as soon as an asymmetrical voltage failure was detect-
ed („Fuse–Failure–Monitor“, also see Section 2.15.1, margin heading „Fuse Failure
Monitor (Non-symmetrical Voltages))“ or when the trip of the mcb for voltage trans-
formers has been signalled via the binary input „>FAIL:Feeder VT“ (internal indi-
cation „internal blocking“).
During single-pole dead time the stages of the negative sequence overvoltage protec-
tion are automatically blocked since arising negative sequence values are only influ-
enced by the asymmetrical power flow, not by the fault in the system. If the device co-
operates with an external automatic reclosure function, or if a single-pole tripping can
be triggered by a different protection system (working in parallel), the overvoltage pro-
tection for the negative sequence system must be blocked via a binary input during
single-pole tripping.
Overvoltage zero
sequence system
3U
0
Figure 2-57 depicts the logic diagram of the zero sequence voltage stage. The funda-
mental frequency is numerically filtered from the measuring voltage so that the har-
monics or transient voltage peaks remain largely harmless.
The triple zero sequence voltage 3·U
0
is fed to the two threshold stages 3U0> and
3U0>>. Combined with the associated time delays T 3U0> and T 3U0>> these stages
form a two-stage overvoltage protection for the zero sequence system. Here too, the
drop-off to pickup ratio can be set (3U0>(>) RESET). Furthermore, a restraint delay
can be configured which is implemented by repeated measuring (approx. 3 periods).
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals