EasyManuals Logo

Siemens SIPROTEC 7SD610 User Manual

Siemens SIPROTEC 7SD610
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #162 background imageLoading...
Page #162 background image
2 Functions
162
7SD610 Manual
C53000-G1176-C145-4
Note
For overvoltage protection it is particularly important to observe the setting hints:
NEVER set an overvoltage stage (U
L-E
, U
L-L
, U
1
) lower than an undervoltage stage.
This would put the device immediately into a state of permanent pickup which cannot
be reset by any measured value operation. As a result, operation via DIGSI or via the
front display would be impossible due to the permanent pickup!
Phase-earth over-
voltage
The phase voltage stages can be switched ON or OFF in address 3701 Uph-e>(>).
In addition to this, you can set Alarm Only, i.e. these stages operate and send
alarms but do not generate any trip command. The setting U>Alarm U>>Trip
creates in addition also a trip command only for the U>> stage.
The settings of the voltage threshold and the timer values depend on the type of ap-
plication. To detect steady-state overvoltages on long lines carrying no load, set the
Uph-e> stage (address 3702) to at least 5 % above the maximum stationary phase-
earth voltage expected during operation. Additionally, a high dropout to pickup ratio is
required (address 3709 Uph-e>(>) RESET = 0.98 presetting). This parameter can
only be altered in DIGSI at Display Additional Settings. The delay time T Uph-e>
(address 3703) should be a few seconds so that overvoltages with short duration may
not result in tripping.
The U
ph
>> stage (address 3704) is provided for high overvoltages with short duration.
Here an adequately high pickup value is set, e.g. the 1
1
/
2
-fold of the nominal phase-
earth voltage. 0.1 s to 0.2 s are sufficient for the delay time T Uph-e>> (address
3705).
Phase-phase over-
voltage
Basically, the same considerations apply as for the phase voltage stages. These
stages may be used instead of the phase voltage stages or be used additionally. De-
pending on your choice, set address 3711 Uph-ph>(>) to ON, OFF, Alarm Only or
U>Alarm U>>Trip.
As phase–to–phase voltages are monitored, the phase–to–phase values are used for
the settings Uph-ph> (address 3712) and Uph-ph>> (address 3714).
For the delay times T Uph-ph> (address 3713) and T Uph-ph>> (address 3715)
the same considerations apply as above. The same is true for the dropout ratios (ad-
dress 3719 Uphph>(>) RESET). The latter setting can only be altered in DIGSI at
Display Additional Settings.
Overvoltage posi-
tive sequence
systemU
1
You can use the positive sequence voltage stages instead of or in addition to previous-
ly mentioned overvoltage stages. Depending on your choice, set address 3731
U1>(>) to ON, OFF, Alarm Only or U>Alarm U>>Trip.
For symmetrical voltages an increase of the positive sequence system corresponds to
an AND gate of the voltages. These stages are particularly suited to the detection of
steady-state overvoltages on long, weak-loaded transmission lines (Ferranti effect).
Here too, the U1> stage (address 3732) with a longer delay time T U1> (address
3733) is used for the detection of steady-state overvoltages (some seconds), the
U1>> stage (address 3734) with the short delay time T U1>> (address 3735) is used
for the detection of high overvoltages that may jeopardise insulation.
Note that the positive sequence system is established according to its defining equa-
tion U
1
=
1
/
3
·|U
L1
+a·U
L2
+a
2
·U
L3
|. For symmetrical voltages this is equivalent to a
phase-to-earth voltage.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals