4 Technical Data
324
7SD610 Manual
C53000-G1176-C145-4
System Interface (optional)
RS232/RS485/FO
Profibus DP RS485/
Profibus DP FO
DNP3.0/MODBUS RS485
DNP3.0/MODBUS FO
Ethernet EN100
Acc. to ordered variant
Isolated interface for data transfer to a master terminal
RS232
Connection for flush mounting housing Rear panel, slot „B“,
9-pole D-subminiature female connector
For Panel Surface-Mounted Case in console housing at case bottom
9-pole D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission speed Min. 4800 Baud; max. 38400 Baud
Factory setting 19200 Baud
Maximum Distance of Transmission Max. 15 m
RS485
Connection for flush mounting housing Rear panel, slot „B“,
9-pole D-subminiature female connector
For Panel Surface-Mounted Case in console housing at case bottom
9-pole D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission speed min. 4800 Baud; max. 38400 Baud;
Factory setting 19200 Bd
Bridgeable distance Max. 1 km
Fibre optic cable (FO)
FOC connector type ST connector
Connection for flush mounting housing rear panel, mounting location „B“
For Panel Surface-Mounted Case in console housing at case bottom
Optical wavelength λ = 820 nm
Laser Class I according to EN 60825-1/-2 Using glass fibre 50/125 µm or
Using glass fibre 62.5/125 µm
Permissible path attenuation Max. 8 dB, with glass fibre 62.5/125 µm
Maximum Distance of Transmission Max. 1.5 km
Character Idle State Selectable, factory setting „Light off“
Profibus DP RS485
Connection for flush mounting housing Rear panel, slot „B“,
9-pole D-subminiature female connector
For Panel Surface-Mounted Case in console housing at case bottom
9-pole D-subminiature female connector
Test voltage 500 V; 50 Hz
Transmission speed up to 12 MBd
Maximum Distance of Transmission 1,000 m (1640 ft.) at ≤ 93.75 kBd
500 m (1640 ft.) at ≤ 187.5 kBd
200 m (328 ft.) at ≤ 1.5 MBaud
100 m (328 ft.) at ≤ 12 MBaud
www . ElectricalPartManuals . com