4.15 User defined functions (CFC)
357
7SD610 Manual
C53000-G1176-C145-4
General limits
MV_SET_STATUS Measured value with status,
encoder
XX X X
NAND NAND - Gate X X X X
NEG Negator X X X X
NOR NOR - Gate X X X X
OR OR - Gate X X X X
REAL_TO_DINT Real after DoubleInt,
adapter
XX X X
REAL_TO_UINT Real after U-Int, adapter X X X X
RISE_DETECT Rising edge detector X X X X
RS_FF RS- Flipflop – X X X
RS_FF_MEMO Status memory for restart X X X X
SI_GET_STATUS Information status single
point indication, decoder
XX X X
SI_SET_STATUS Single point indication with
status, encoder
XX X X
SQUARE_ROOT Root Extractor X X X X
SR_FF SR- Flipflop – X X X
SR_FF_MEMO Status memory for restart X X X X
ST_AND AND gate with status X X X X
ST_NOT Negator with status X X X X
ST_OR OR gate with status X X X X
SUB Substraction X X X X
TIMER Timer – X X –
TIMER_SHORT Simple timer – X X –
UINT_TO_REAL U-Int to real, adapter X X X X
UPPER_SETPOINT Upper Limit X – – –
X_OR XOR - Gate X X X X
ZERO_POINT Zero Supression X – – –
Description Limit Comments
Maximum number of all CFC charts considering all task
levels
32 When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into monitoring
mode. The red ERROR-LED lights up.
Maximum number of all CFC charts considering one task
level
16 Only error message
(evolving error in processing procedure)
Maximum number of all CFC inputs considering all charts 400 When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device starts monitoring.
The red ERROR-LED lights up.