A.8 Information List
409
7SD610 Manual
C53000-G1176-C145-4
6856 >Trip circuit superv. 2: Trip Relay
(>TripC2 TripRel)
TripCirc.Superv SP ON
OFF
**LEDBIBO
6857 >Trip circuit superv. 2: Breaker
Relay (>TripC2 Bkr.Rel)
TripCirc.Superv SP ON
OFF
**LEDBIBO
6858 >Trip circuit superv. 3: Trip Relay
(>TripC3 TripRel)
TripCirc.Superv SP ON
OFF
**LEDBIBO
6859 >Trip circuit superv. 3: Breaker
Relay (>TripC3 Bkr.Rel)
TripCirc.Superv SP ON
OFF
**LEDBIBO
6861 Trip circuit supervision OFF
(TripC OFF)
TripCirc.Superv OUT ON
OFF
* * LED BO 170 53 1 Yes
6865 Failure Trip Circuit (FAIL: Trip cir.) TripCirc.Superv OUT ON
OFF
* * LED BO 192 36 1 Yes
6866 TripC1 blocked: Binary input is
not set (TripC1 ProgFAIL)
TripCirc.Superv OUT ON
OFF
**LEDBO
6867 TripC2 blocked: Binary input is
not set (TripC2 ProgFAIL)
TripCirc.Superv OUT ON
OFF
**LEDBO
6868 TripC3 blocked: Binary input is
not set (TripC3 ProgFAIL)
TripCirc.Superv OUT ON
OFF
**LEDBO
7104 >BLOCK Backup OverCurrent
I>> (>BLOCK O/C I>>)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 4 1 Yes
7105 >BLOCK Backup OverCurrent I>
(>BLOCK O/C I>)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 5 1 Yes
7106 >BLOCK Backup OverCurrent Ip
(>BLOCK O/C Ip)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 6 1 Yes
7107 >BLOCK Backup OverCurrent
Ie>> (>BLOCK O/C Ie>>)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 7 1 Yes
7108 >BLOCK Backup OverCurrent
Ie> (>BLOCK O/C Ie>)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 8 1 Yes
7109 >BLOCK Backup OverCurrent
Iep (>BLOCK O/C Iep)
Back-Up O/C SP ON
OFF
* * LED BI BO 64 9 1 Yes
7110 >Backup OverCurrent Instanta-
neousTrip (>O/C InstTRIP)
Back-Up O/C SP ON
OFF
ON
OFF
* LED BI BO 64 10 1 Yes
7111 >BLOCK direct. Backup Over-
Current I> (>BLOCK Dir. I>)
Back-Up O/C SP ON
OFF
**LEDBIBO64111Yes
7112 >BLOCK direct. Backup Over-
Current Ip (>BLOCK Dir. Ip)
Back-Up O/C SP ON
OFF
**LEDBIBO64121Yes
7113 >BLOCK direct. Backup Over-
Current Ie> (>BLOCK Dir. Ie>)
Back-Up O/C SP ON
OFF
**LEDBIBO64131Yes
7114 >BLOCK direct. Backup Over-
Current Iep (>BLOCK Dir. Iep)
Back-Up O/C SP ON
OFF
**LEDBIBO64141Yes
7130 >BLOCK I-STUB (>BLOCK I-
STUB)
Back-Up O/C SP ON
OFF
**LEDBIBO64301Yes
7131 >Enable I-STUB-Bus function (>I-
STUB ENABLE)
Back-Up O/C SP ON
OFF
ON
OFF
* LED BI BO 64 31 1 Yes
7132 >BLOCK Backup OverCurrent
Ie>>> (>BLOCK O/CIe>>>)
Back-Up O/C SP ON
OFF
**LEDBIBO64321Yes
7151 Backup O/C is switched OFF
(O/C OFF)
Back-Up O/C OUT ON
OFF
**LEDBO64511Yes
7152 Backup O/C is BLOCKED (O/C
BLOCK)
Back-Up O/C OUT ON
OFF
ON
OFF
* LED BO 64 52 1 Yes
7153 Backup O/C is ACTIVE (O/C
ACTIVE)
Back-Up O/C OUT * * * LED BO 64 53 1 Yes
7161 Backup O/C PICKED UP (O/C
PICKUP)
Back-Up O/C OUT * OFF m LED BO 64 61 2 Yes
7162 Backup O/C PICKUP L1 (O/C
Pickup L1)
Back-Up O/C OUT * ON * LED BO 64 62 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com