10271 3U0>> Pickup (3U0>> Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 71 2 Yes
10272 3U0> TimeOut (3U0> TimeOut) Voltage Prot. OUT * * * LED BO
10273 3U0>> TimeOut (3U0>> Time-
Out)
Voltage Prot. OUT * * * LED BO
10274 3U0>(>) TRIP command
(3U0>(>) TRIP)
Voltage Prot. OUT * ON * LED BO 73 74 2 Yes
10280 U1> Pickup (U1> Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 80 2 Yes
10281 U1>> Pickup (U1>> Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 81 2 Yes
10282 U1> TimeOut (U1> TimeOut) Voltage Prot. OUT * * * LED BO
10283 U1>> TimeOut (U1>> TimeOut) Voltage Prot. OUT * * * LED BO
10284 U1>(>) TRIP command (U1>(>)
TRIP)
Voltage Prot. OUT * ON * LED BO 73 84 2 Yes
10290 U2> Pickup (U2> Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 90 2 Yes
10291 U2>> Pickup (U2>> Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 91 2 Yes
10292 U2> TimeOut (U2> TimeOut) Voltage Prot. OUT * * * LED BO
10293 U2>> TimeOut (U2>> TimeOut) Voltage Prot. OUT * * * LED BO
10294 U2>(>) TRIP command (U2>(>)
TRIP)
Voltage Prot. OUT * ON * LED BO 73 94 2 Yes
10300 U1< Pickup (U1< Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 100 2 Yes
10301 U1<< Pickup (U1<< Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 101 2 Yes
10302 U1< TimeOut (U1< TimeOut) Voltage Prot. OUT * * * LED BO
10303 U1<< TimeOut (U1<< TimeOut) Voltage Prot. OUT * * * LED BO
10304 U1<(<) TRIP command (U1<(<)
TRIP)
Voltage Prot. OUT * ON * LED BO 73 104 2 Yes
10310 Uph-e< Pickup (Uph-e< Pickup) Voltage Prot. OUT * ON
OFF
* LED BO 73 110 2 Yes
10311 Uph-e<< Pickup (Uph-e<<
Pickup)
Voltage Prot. OUT * ON
OFF
* LED BO 73 111 2 Yes
10312 Uph-e<(<) Pickup L1 (Uph-e<(<)
PU L1)
Voltage Prot. OUT * ON
OFF
* LED BO 73 112 2 Yes
10313 Uph-e<(<) Pickup L2 (Uph-e<(<)
PU L2)
Voltage Prot. OUT * ON
OFF
* LED BO 73 113 2 Yes
10314 Uph-e<(<) Pickup L3 (Uph-e<(<)
PU L3)
Voltage Prot. OUT * ON
OFF
* LED BO 73 114 2 Yes
10315 Uph-e< TimeOut (Uph-e< Time-
Out)
Voltage Prot. OUT * * * LED BO
10316 Uph-e<< TimeOut (Uph-e<< Tim-
eOut)
Voltage Prot. OUT * * * LED BO
10317 Uph-e<(<) TRIP command (Uph-
e<(<) TRIP)
Voltage Prot. OUT * ON * LED BO 73 117 2 Yes
10318 Uph-e< Pickup L1 (Uph-e< PU
L1)
Voltage Prot. OUT * * * LED BO
10319 Uph-e< Pickup L2 (Uph-e< PU
L2)
Voltage Prot. OUT * * * LED BO
10320 Uph-e< Pickup L3 (Uph-e< PU
L3)
Voltage Prot. OUT * * * LED BO
10321 Uph-e<< Pickup L1 (Uph-e<< PU
L1)
Voltage Prot. OUT * * * LED BO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation