SIRIUS 3RT2 contactors/contactor assemblies   
2.4 Configuration 
  SIRIUS Innovations 
132  System Manual, 01/2011, A8E56203870002-03 
2.4.9  Operation of a motor in two directions of rotation (3RA23 reversing contactor 
assembly) 
Applications 
The 3RA23 reversing contactor assembly is used to operate a motor in two directions of 
rotation. The starting characteristics correspond to those of a direct-on-line starter. When 
used in conjunction with the relevant protective devices, they facilitate the space-saving and 
compact assembly of fused and fuseless feeders. 
On combinations with AC operation, 50/60 Hz, a changeover delay of 50 ms must be 
provided at voltages ≥ 500 V. At voltages ≥ 400 V, a changeover delay of 30 ms is 
recommended. These idle times do not apply to combinations with DC operation.  
Versions 
The 3RA23 reversing contactor assemblies are available with a uniform performance range 
of 3 kW to 18.5 kW (utilization category AC-3). The 3RA23 reversing contactor assemblies 
are 90 mm wide.  
The diagram below shows the fully mounted 3RA23 reversing contactor assembly size S0 
with a screw-type connection system. 
 
Figure 2-8  Reversing contactor assembly with screw-type connection system (size S0) 
Reference 
 
More information ...  Can be found in the chapter titled ... 
About the individual components for customers to 
assemble their own 3RA23 reversing contactor 
assembly and how to mount said assembly. 
Assembly kit for reversing contactor assemblies 
(Page 212) 
Rated powers 
The performance range of the 3RA23 reversing contactor assembly in size S00 extends up 
to 7.5 kW at a voltage of 400 V. In size S0, the maximum power value is 18.5 kW at a 
voltage of 400 V.