386  System Manual, 01/2011, A8E56203870002-03 
4.4  Functions 
3RV2 motor starter protectors meet the requirements for motor and system protection 
according to IEC 60947-2 / DIN VDE 0660-101. 
Motor and system protection is achieved using the following functions: 
●  Overload protection 
●  Short-circuit protection 
●  Phase loss sensitivity 
4.4.1  Overload and short-circuit protection 
Overload protection 
The current of the motor requiring protection is set on the setting scale. This sets the 
integrated overload protection to the motor current. 
Short-circuit protection 
The short-circuit release is factory-set to a value that is 13 times the rated current of the 
motor starter protector (upper setting scale). This ensures problem-free ramping-up and safe 
protection for the motor. 
Release 
3RV2 motor starter protectors are fitted with the following releases: 
●  Inverse-time delayed thermal overload release (except for the 3RV23) 
●  Instantaneous short-circuit release 
The overload releases can be set to the load feeder. 
 
 
Note 
Motor starter protectors for transformer protection 
The motor starter protectors and circuit breakers for transformer protection (3RV24, 3RV28) 
are set to 20 times the rated current to prevent undesirable tripping due to the high inrush 
current.