SIRIUS 3RU2/3RB3 overload relays 
  5.5 Configuration 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
505 
5.5.1.3  Contactor assembly for star-delta (wye-delta) start 
Overload relays in contactor assemblies for star-delta (wye-delta) start 
When using overload relays in conjunction with contactor assemblies for star-delta (wye-
delta) start, you need to bear in mind that only 1/√3 times the motor current flows through the 
line contactor. An overload relay mounted onto a line contactor has to be set to this 0.58-
times motor current. 
 
NOTICE 
 
Internal ground-fault detection on the 3RB31 
If you are using the 3RB31 solid-state overload relay in conjunction with contactor 
assemblies for star-delta (wye-delta) start, internal ground-fault detection must not be 
activated due to the occurrence of transient current peaks when switching over from star 
(wye) to delta operation. These can cause ground-fault monitoring to respond. 
 
5.5.1.4  Operation with frequency converters 
3RU21 thermal overload relays 
3RU21 thermal overload relays are suitable for operation with frequency converters. 
Depending on the frequency of the converter, eddy current and skin effects that occur mean 
that in some cases, a current higher than the motor current has to be set. 
3RB30/3RB31 solid-state overload relays 
3RB30/3RB31 solid-state overload relays are suitable for frequencies of 50/60 Hz and their 
associated harmonics. This makes it possible to use a 3RB30/3RB31 on the input side of the 
frequency converter. If motor protection is required on the outgoing side of the frequency 
converter, we recommend the 3RN thermistor motor protection devices or 3RU21 thermal 
overload relays. 
Reference 
 
More information ...  Can be found in the chapter titled ... 
About the currents to be set  Project guidelines for use downstream of 
frequency converters/inverters with pulsed 
voltage (Page 398)