SIRIUS 3RR2 current monitoring relays 
  8.7 Connection 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
703 
8.7.2  3RR22 Standard digital setting current monitoring relay 
Connection of terminals 
Depending on their design, the current monitoring relays are supplied with a 24 V AC/DC or 
24 to 240 V AC/DC supply via terminals B1/B2. 
The current monitoring relays monitor an AC load current (apparent current I
s
 or active 
current I
p
) which flows through device terminals 1L1/2T1, 3L2/4T2, and 5L3/6T3. The current 
monitoring relay has two separate outputs which respond to separate threshold values. 
In accordance with the configuration the system is monitored for overshoot (I▲ CO contact, 
I!▲ semiconductor output) or undershoot (I▼ CO contact, I!▼ semiconductor output), or values 
are checked within a window range (I▲ , I!▲ and I▼ , I!▼ ≠ OFF).  
 
Terminal  Designation 
B1  Supply voltage ∼/+ 
B2  Supply voltage ∼/- 
Q  Semiconductor output, e.g. for pre-warning threshold 
32  Output relay CO contact NC contact, e.g. for alarm threshold 
31  Output relay CO contact root, e.g. for alarm threshold 
34  Output relay CO contact NO contact, e.g. for alarm threshold 
2T1 
4T2 
6T3 
Main circuit terminals 
14/22  Feed-through contactor auxiliary switch (S00) 
A2  Feed-through contactor coil terminal (S00) 
Reference 
 
More information ...  Can be found in the chapter titled ... 
About connecting the SIRIUS modular system  System overview, under "Connection (Page 74)" 
About connection terminals  3RR224.-.F.30 Standard digital setting current 
monitoring relay (Page 688) 
About conductor cross-sections and tightening 
torques 
Conductor cross-sections main circuit (Page 747)