SIRIUS 3RV2 motor starter protectors   
4.10 Technical data 
  SIRIUS Innovations 
458  System Manual, 01/2011, A8E56203870002-03 
4.10.7  Auxiliary releases 
 
  Undervoltage release  Shunt release 
Power input 
  During pick-up 
- Alternating voltages  VA/W  20.2 / 13  20.2 / 13  
- Direct voltages  W  20  13 ... 80 
  During continuous operation 
- Alternating voltages  VA/W  7.2 / 2.4  --  
- Direct voltages  W  2.1  -- 
Response voltage 
  Tripping 
V  0.35 to 0.7 x U
s
  0.7 to 1.1 x U
s
 
  Pick-up 
V  0.85 to 1.1 x U
s
  -- 
Maximum opening time   ms  20 
4.10.8  Short-circuit protection for auxiliary and control circuits 
 
  Undervoltage release  Shunt release 
gL/gG melting fuses  A  10 
Miniature circuit breaker, C characteristic  A  6
1)
 
1)
  Prospective short-circuit current < 0.4 kA