SIRIUS 3RR2 current monitoring relays 
  8.6 Mounting 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
699 
8.6  Mounting 
8.6.1  Mounting options 
3RR2 current monitoring relays are matched to 3RT2 contactors and 3RF34 (S0) solid-state 
contactors in terms of their electrical and mechanical features. As a result, direct mounting 
can be achieved easily. 
Alternatively, the devices can also be installed individually in the case of stand-alone 
assembly or if a 3RU2/3RB3 overload relay is being used at the same time. 
8.6.2  Minimum clearances and mounting positions 
Minimum clearance 
A minimum lateral clearance of > 6 mm must be maintained from grounded parts. 
Mounting position 
It can be mounted in any position. 
8.6.3  Mounting/Disassembly 
Direct mounting on 3RT2 contactor/3RF34 (S0) solid-state contactor 
The diagram below shows an example mounting scenario based on mounting the 
3RR21 analog setting current monitoring relay, size S0, on the 3RT2 contactor. 
Table 8- 3  Mounting of 3RR2 current monitoring relay, screw-type connection system (S0) 
Step  Operating instruction  Figure 
1  Push the current monitoring relay into the 
contactor from below. Attach the two hooks 
on the current monitoring relay to the two 
openings on the rear of the contactor. This 
pushes the main current contacts into the 
corresponding terminals on the contactor. 
2  Tighten the screws on the contactor with a 
Pozidriv size 2 (S00) or Pozidriv size 3 (S0) 
screwdriver (tightening torque 0.8 to 1.2 Nm).
Check that the cable is clamped tight.