SIRIUS 3RT2 contactors/contactor assemblies 
  2.8 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
245 
2.8.1.8  Actuation - 3RT202. contactors 
Table 2- 86  Actuation - 3RT202. contactors 
Type  3RT2023...25  3RT2026...28 
Size  S0 
Actuation 
Magnet coil operating range  
  AC/DC 
0.8 to 1.1 x U
S
 
Magnet coil power input (for cold coil and 1.0 x U
S
)   
  AC operation, 50 Hz, standard version 
- Switch-on power  VA  65  77 
- cos ϕ    0.82  0.82 
- Holding power  VA  8.5  9.8 
 
- cos ϕ    0.25  0.25 
  AC operation, 50/60 Hz, standard version 
- Switch-on power  VA  68 / 67  81 / 79 
- cos ϕ    0.72 / 0.74  0.72 / 0.74 
- Holding power  VA  9.1 / 7.4  10.5 / 8.5 
 
- cos ϕ    0.25 / 0.28  0.25 / 0.28 
  AC operation, 50 Hz, USA/Canada 
- Switch-on power  VA  65  77 
- cos ϕ    0.82  0.82 
- Holding power  VA  8.5  9.8 
 
- cos ϕ    0.25  0.25 
  AC operation, 60 Hz, USA/Canada 
- Switch-on power  VA  73  87 
- cos ϕ    0.76  0.76 
- Holding power  VA  8.2  9.4 
 
- cos ϕ    0.28  0.28 
  DC operation 
  - Switch-on power = holding power  W  5.9 
Permissible residual current of electronics (with 0 signal) 
  AC operation 
mA  < 6 mA x (230 V/U
S
)  < 7 mA x (230 
V/U
S
) 
  DC operation 
mA  < 16 mA x (24 V/U
S
)