SIRIUS 3RU2/3RB3 overload relays   
5.10 Technical data 
  SIRIUS Innovations 
536  System Manual, 01/2011, A8E56203870002-03 
5.10  Technical data 
5.10.1  Performance features 
5.10.1.1  General data 
Table 5- 33  General data for 3RU21 and 3RB30/3RB31 overload relays 
Feature  Description  3RU21  3RB30/3RB31 
Sizes 
  Are matched to the dimensions, 
connections and technical features of the 
other devices in the SIRIUS modular 
system (contactors, soft starters, etc.) 
  Permit the mounting of slim-line and 
compact load feeders in widths of 45 mm 
(S00), 45 mm (S0) 
  Make configuration easier 
S00/S0  S00/S0 
Seamless current range 
  Allows straightforward and consistent 
configuration with one series of overload 
relays (for small to large loads) 
0.11 to 40 A  0.1 to 40 A 
 
5.10.1.2  Protection functions - overview 
Table 5- 34  Protection functions supported by 3RU21 and 3RB20/3RB31 overload relays 
Feature  Description  3RU21  3RB30/3RB
31 
Tripping in the event of overload 
  Provides optimum current-dependent protection of 
loads against impermissibly high temperature rise 
due to overload 
✓  ✓ 
Tripping in the event of phase 
asymmetry 
  Provides optimum current-dependent protection of 
loads against impermissibly high temperature rise 
due to phase asymmetry 
✓  ✓ 
Tripping in the event of phase failure 
  Minimizes the temperature rise of the three-phase 
motor in the event of a phase failure 
✓  ✓ 
Protection of single-phase loads 
  Enables single-phase loads to be protected 
✓  -- 
Tripping in the event of ground fault 
by means of 
internal ground-fault detection (can 
be activated) 
  Provides optimum protection of loads in the event 
of high-impedance faults to ground caused by 
moisture, condensation, damaged insulation, etc. 
  Eliminates the need for additional special 
equipemnt 
  Saves space in the control cabinet 
  Reduces wiring outlay and costs 
--  ✓ 
(3RB31 
only)