SIRIUS 3RV2 motor starter protectors 
  4.10 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
457 
4.10.5  Auxiliary switches, transverse, solid-state compatible 
 
  1 CO contact 
Rated operational voltage U
e
 alternating voltage  V  125 
Rated operational current I
e
/AC-14 at U
e 
= 125 V  A  0.1 
Rated operational voltage U
e
 direct voltage L/R 200 ms  V  60 
Rated operational current I
e 
/DC-13 at U
e
 = 60 V  A  0.3 
V  5 Minimum load capacity 
mA  1 
 
4.10.6  Auxiliary switches, lateral and signaling switches 
 
  Switching capacity for different voltages:  
Lateral auxiliary switch 1 NO + 1 NC, 2 NO, 2 NC, 2 NO +2  NC;  
signaling switch 
Rated operational current I
e
 
  AC-15, alternating voltage 
- 24 V  A  6 
- 230 V  A  4 
- 400 V  A  3 
 
- 690 V  A  1 
  AC-12 = 
I
th
, alternating voltage 
- 24 V  A  10 
- 230 V  A  10 
- 400 V  A  10 
 
- 690 V  A  10 
  DC, direct voltage 
L/R 
200 ms 
- 24 V  A  2 
- 110 V  A  0.5 
- 220 V  A  0.25 
 
- 440 V  A  0.1 
V  17 Minimum load capacity  
mA  1