SIRIUS 3RA28 function modules for mounting on 3RT2 contactors 
  7.4 Functions 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
655 
7.4.2.4  Star-delta (wye-delta) function 
Contacts  
The function module (comprising basic module with integrated control logic and 2 coupling 
modules) has 2 internal NO contacts. 
Time ranges 
The start time in star operation can be set between 0.5 and 60 s. The changeover delay is 
set to a non-adjustable value of 50 ms. 
Function chart  
 
3RA2816-0EW20 
VV PV
<4
˂4
4
 
Method of operation 
The function module for star-delta (wye-delta) start is responsible for the electrical interlock 
and the timing relay function (dead interval from star (wye) operation to delta operation). 
Control is exclusively via A1/A2 on the line contactor below. Additional wiring is therefore not 
required. The supply voltage is routed via a ribbon cable, eliminating the need for control 
circuit wiring. 
The instantaneous star contact and the time-delayed delta contact share the same contact 
root. 
To avoid inter-phase short circuits, the changeover delay from star (wye) to delta is 50 ms.