SIRIUS 3RF34 solid-state switching devices   
3.11 Technical data 
  SIRIUS Innovations 
356  System Manual, 01/2011, A8E56203870002-03 
Reference 
 
More information ...  Can be found in the chapter titled ... 
About connection systems and terminal 
designations 
Connection (Page 344) 
3.11.6  Solid-state contactors - fuseless design with CLASS 10 motor starter protector 
Fuseless design with CLASS 10 motor starter protector 
Table 3- 36  Main circuit 
 Order no.    3RF34 05-.BB..  3RF34 10-.BB..  3RF34 12-.BB..  3RF34 16-.BB.. 
Rated operational current 
I
AC-53
1)
 acc. to IEC 60947-4-2 
At 40 °C  A  5.2 (4.5) 
2)
  9.2  12.5  16 
UL/CSA at 50 °C  A  4.6 (4.0) 
2)
  8.4  11.5  14 
At 60 °C  A  4.2 (3.5) 
2
  7.6  10.5  12.5 
Power loss at 
I
AC-53
 at 40 °C  W  10 (8) 
2)
  16  22  28 
Short-circuit protection with type of coordination "1" at operational voltage 
U
e
 up to 440 V 
Motor starter protector  Type  3RV20 11-1GA10  3RV20 11-1JA10  3RV20 11-1KA10  3RV20 11-4AA10
I
q
  kA  50  5  5  3 
1)
  Use overvoltage protection device; max. cut-off-voltage 6,000 V; min. energy handling capability 100 J 
2)
  The reduced values in brackets apply in the case of a directly mounted motor starter protector combined with side-by-
side mounting.