1.9.2.3  Conductor cross-sections for ring cable lug connection system 
Conductor cross-sections for ring cable lug connection system 
The tables below define the permissible conductor cross-sections for main terminals and 
auxiliary conductor connections in sizes S00 and S0 for ring cable lug connection systems. 
Table 1- 34  Main conductors and auxiliary conductors of size S00 with M3 combination screws 
    SIRIUS devices 
Tool 
 
Pozidriv size 2, 
Ø 5 to 6 mm 
Tightening torque    0.8 to 1.2 Nm 
d
2
 = min. 3.2 mm Ring cable lug 
1)
 
d
2
d
3
 
d
3
 = max. 7.5 mm 
Table 1- 35  Main conductors and auxiliary conductors of size S0 with M4 combination screws 
    SIRIUS devices 
Tool 
 
Pozidriv size 2, 
Ø 5 to 6 mm 
Tightening torque    2.0 to 2.5 Nm 
d
2
 = min. 4.3 mm Ring cable lug 
1)
 
d
2
d
3
 
d
3
 = max. 12.2 mm 
1)
 The following ring cable lugs are approved for achieving the required clearances and creepage distances: 
●  For applications according to IEC 60947-1: 
–  DIN 46237 (with insulating sleeve) 
–  JIS CS805 type RAV (with insulating sleeve) 
–  JIS CS805 type RAP (with insulating sleeve) 
●  For applications according to UL 508: 
–  DIN 46 234 (without insulating sleeve) 
–  DIN 46225 (without insulating sleeve) 
–  JIS CS805 (without insulating sleeve) 
A shrink-on sleeve must be used to insulate ring cable lugs without an insulating sleeve. The following 
conditions must be met: 
●  Application temperature: -55 °C to +155 °C 
●  UL 224 approved 
●  Flame-protected 
 
DANGER 
 
 
Hazardous voltage. 
Will cause death or serious injury. 
Only use approved ring cable lugs to meet the required clearances and creepage 
distances.