SIRIUS 3RR2 current monitoring relays 
  8.8 Operation 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
709 
8.8.1.6  Memory 
Definition of memory  
The "Memory" setting controls how the device behaves following a shutdown due to a fault 
and subsequent return to the normal range. 
There are two possible settings: 
●  Automatic reset (Memory = O) 
If the device is set to automatic reset, the switching contact will respond once the normal 
range plus the hysteresis threshold have been reached. The red FAULT LED goes out. 
The overshoot or undershoot which triggered the response is not saved.  
The hysteresis is set to a fixed value of 6.25% of the set value. 
●  Manual RESET (Memory = I) 
If manual RESET is selected, the switching contact remains in the current switching state 
even if the load current returns to a permissible value. 
 
 
 
 
Note 
Reset with manual RESET 
This saved fault condition can be reset by briefly switching to Memory = O or by 
disconnecting and then reconnecting the supply voltage. 
 
Factory setting 
The device is factory-set to automatic reset. 
Changes to settings 
Move the slide switch (Memory) to toggle the device between automatic reset and manual 
RESET. 
Reference 
For more information, see the chapter titled Hysteresis (Page 718).