SIRIUS 3RR2 current monitoring relays   
8.8 Operation 
  SIRIUS Innovations 
710  System Manual, 01/2011, A8E56203870002-03 
8.8.1.7  Diagnostics with LED 
Status display  
On the analog setting current monitoring relay, two status LEDs indicate the operating state: 
●  FAULT (red) 
●  READY (green) 
 
Display  Meaning 
FAULT off  Measured value is within range limits 
FAULT steady on  Device has tripped 
FAULT flashing slowly  Delay time is running 
FAULT flashing rapidly  Cable break/phase failure detected 
READY off  No voltage at B1 - B2 
READY on  Voltage at B1 - B2 
You will find more information about the LED display and its various settings in the chapter 
titled Function charts for Basic analog setting current monitoring relay (Page 692
). 
Cable break detected  
The CO contact responds immediately when a cable break is detected (only residual current 
in branch circuit 1L1/2T1 or 3L2/4T2). All running delay times are aborted and the red 
FAULT LED flashes rapidly. If the load current in both circuits falls below the lower range 
limit, the current monitoring relay responds again in accordance with the settings made. If 
Memory = I, the tripping state is saved.