SIRIUS 3RV2 motor starter protectors   
4.10 Technical data 
  SIRIUS Innovations 
454  System Manual, 01/2011, A8E56203870002-03 
4.10.2  3RV2 motor starter protectors 
 
Type  3RV2. 1  3RV2.  2 
Size  S00  S0 
Width  45 mm  45 mm 
Standards 
  IEC 60947-1, EN 60947-1 (VDE 0660 Part 100) 
Yes 
  IEC 60947-2, EN 60947-2 (VDE 0660 Part 101) 
Yes 
  IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102) 
Yes 
  UL 489, CSA C22.2-No.5-02 
Yes 
Number of poles 3 
Max. rated current I
n max 
 
(= max. rated operational current I
e
) 
A  16  40 
Permissible ambient temperature 
  Storage/transport 
°C  –50 ... +80 
... 32 A  °C  –20 ... +70
1)
 
  Operation 
36 to 40 A  °C  -20 ... +40 
Permissible rated current at internal cubicle temperature 
  +60 °C 
%  100 
  +70 °C 
%  87 
Motor starter protector in enclosure ≤ 32 A 
Permissible rated current at housing ambient temperature  
  +35 °C 
%  100 
  +60 °C 
%  87 
Rated operational voltage U
e
 
  acc. to IEC 
V AC  690
2)
 
  acc. to UL/CSA 
V AC  600 
Rated frequency  Hz  50 / 60 
Rated insulation voltage U
i
  V  690 
Rated impulse withstand voltage U
imp
 kV 6 
Utilization category 
  IEC 60947-2 (motor starter protectors) 
A 
  IEC 60947-4-1 (motor starters) 
AC-3 
Tripping class CLASS acc. to IEC 60947-4-1  10 
Direct current short-circuit breaking capacity(time constant t = 5 ms) 
  1 current path 150 V DC 
kA  10 
  2 current paths in series 300 V DC 
kA  10 
  3 current paths in series 450 V DC 
kA  10 
I
n
: ... 0.63 A   W  5 Power loss P
v
 per motor starter 
protector dependent upon rated 
I
n
: 0.8 to 6.3 A  W  6