SIRIUS 3RU2/3RB3 overload relays   
5.10 Technical data 
  SIRIUS Innovations 
540  System Manual, 01/2011, A8E56203870002-03 
Type  3RU21 16  3RU21 26 
Size  S00  S0 
Width  45 mm  45 mm 
Degree of protection acc. to IEC 60529  IP20 
Touch protection acc. to IEC 61140  Screw connection and spring-loaded terminals: finger-safe 
Ring cable lug connection: finger-safe only with optional 
terminal covers 
Shock resistance with sine 
acc. to IEC 60068-2-27 
g/ms  8 / 10 
Electromagnetic compatibility (EMC) -  Immunity 
  Conducted interference suppression 
- Burst acc. to IEC 61000-4-4  
(corresponds to severity 3) 
kV  EMC immunity is not relevant in the case of thermal overload 
relays 
 
- Surge acc. to IEC 61000-4-5  
(corresponds to severity 3) 
kV  EMC immunity is not relevant in the case of thermal overload 
relays 
  Electrostatic discharge acc. to 
IEC 61000-4-2  
(corresponds to severity 3) 
kV  EMC immunity is not relevant in the case of thermal overload 
relays 
  Field-related interference suppression to 
IEC 61000-4-3  
(corresponds to severity 3) 
V/m  EMC immunity is not relevant in the case of thermal overload 
relays 
Electromagnetic compatibility (EMC)  
- Emitted interference 
EMC immunity is not relevant in the case of thermal overload 
relays 
Resistance to extreme climates - Humidity  %  90 
Dimensions  See Dimension drawings (dimensions in mm) (Page 552) 
Installation altitude above sea level  m  Up to 2,000; above this, please contact us 
Mounting position  See Minimum clearances and mounting position (Page 508) 
Type of fixing  Direct mounting/stand-alone assembly with terminal support
2)
 
1)
  Remote RESET in conjunction with the appropriate accessory 
2) 
  For screw and snap-on mounting onto DIN rail TH 35 
5.10.2.2  Main circuit 
Table 5- 39  Technical data for the main circuit, 3RU21 overload relays 
Type  3RU21 16  3RU21 26 
Size  S00  S0 
Width  45 mm  45 mm 
Rated insulation voltage U
i
 
(pollution degree 3) 
V  690 
Rated impulse withstand voltage U
imp
 kV 6 
Rated operational voltage U
e
  V  690 
Type of current 
  DC current 
Yes 
  AC current 
Yes, frequency range up to 400 Hz