SIRIUS 3RT2 contactors/contactor assemblies 
  2.8 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
267 
2.8.3.2  Coupling relays 
3RH21 auxiliary coupling relays for switching auxiliary circuits 
Technical data for 3RH21 auxiliary coupling relays 
Unless listed below, the technical data is the same as that for 3RH21 auxiliary contactor 
relays. 
Table 2- 106  Technical data for 3RH21..-.HB40, 3RH21..-.JB40, 3RH21..-.KB40 contactors 
Type  3RH21..-.HB40  3RH21..-.JB40  3RH21..-.KB40 
Size  S00 
Magnet coil operating range  0.7 to 1.25 x U
S
 
Magnet coil power input (with cold 
coil) 
 
Switch-on power = holding power   
At U
S
 = 17 V  W  1.4 
At U
S
 = 24 V  W  2.8 
At U
S
 = 30 V  W  4.4 
Permissible residual current 
 of electronics with 0 signal 
  < 10 mA x (24 V/U
S
) 
Magnet coil suppressor circuit  Without 
overvoltage 
attenuation 
 
 
With diode 
 
Suppressor diode 
 
Switching times 
Switching on at 17 V 
- ON-delay NO  ms  40 ... 130  
- OFF-delay NC  ms  30 ... 80 
At 24 V 
- ON-delay NO  ms  35 ... 60  
- OFF-delay NC  ms  25 ... 40 
At 30 V 
- ON-delay NO  ms  25 ... 50  
- OFF-delay NC  ms  13 ... 30 
Switching off at 17 to 30 V 
- OFF-delay NO  ms  70 ... 20  38 ... 65  7 ... 20  
- ON-delay NC  ms  20 ... 30  55 ... 75  20 ... 30 
Vertical mounting position  Please contact your local Siemens office for advice