2.8.1.11  Main circuit - 3RT202. contactors (current carrying capacity for direct current) 
Table 2- 90  Main circuit - Current carrying capacity for direct current (3RT202. contactors) 
Type  3RT20 
23 
3RT20 
24 
3RT20 
25 
3RT20 
26 
3RT20 
27 
3RT20 
28 
Size  S0 
Main circuit - Current carrying capacity for direct current 
Utilization category DC-1, switching resistive loads (L/R ≤1 ms) 
  Rated operational current I
e
(at 60 °C) 
Up to 24 V  A  35 
60 V  A  20 
110 V  A  4.5 
220 V  A  1 
440 V  A  0.4 
- 1 current path 
600 V  A  0.25 
Up to 24 V  A  35 
60 V  A  35 
110 V  A  35 
220 V  A  5 
440 V  A  1 
- 2 current paths in series 
600 V  A  0.8 
Up to 24 V  A  35 
60 V  A  35 
110 V  A  35 
220 V  A  35 
440 V  A  2.9 
 
- 3 current paths in series 
600 V  A  1.4 
Utilization category DC-3 and DC-5, shunt-wound and series-wound motors (L/R ≤ 15 ms) 
Rated operational current I
e
(at 60 °C) 
Up to 24 V  A  20 
60 V  A  5 
110 V  A  2.5 
220 V  A  1 
440 V  A  0.09 
  - 1 current path 
600 V  A  0.06 
Up to 24 V  A  35 
60 V  A  35 
110 V  A  15 
220 V  A  3 
440 V  A  0.27 
  - 2 current paths in series 
600 V  A  0.16