SIRIUS 3RT2 contactors/contactor assemblies 
  2.8 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
229 
Type  3RT2 
Size  S00  S0 
Rated data for auxiliary contacts   
Rated operational current I
e
/DC-13 
24 V  A  6
2)
 
60 V  A  2 
110 V  A  1 
125 V  A  1 
220 V  A  0.3 
440 V  A  0.14 
  at rated operational voltage U
e
 
600 V  A  0.1 
Contact reliability at 17 V, 1 mA 
acc. to DIN EN 60947-5-4 
Frequency of contact faults <10
-8
 i.e. < 
1 fault per 100 million operating cycles 
1) 
  Integrated auxiliary contacts (size S0) and contacts in the auxiliary switch blocks for contactors (size S00 and S0): 6 A 
2) 
  Contacts in auxiliary switch blocks for contactors size S00 and S0:4 A