Fuse ratings for solid-state reversing contactors 
Table 3- 13  Fuses for protecting against high short-circuit currents 
  Fuses     
3RF34  Max. size [A]  Class  Type  Current [kA]  Voltage [V] 
3RF3403-.BD  45  J   TD  65  480 
3RF3405-.BD  45  J   TD  65  480 
3RF3410-.BD  45  J   TD  65  480 
Circuit breakers for protecting against high short-circuit currents 
Table 3- 14  Circuit breaker ratings for solid-state contactors 
  Fuses     
3RF34  Max. size [A]  Type  Current [kA]  Voltage [V] 
3RF3405-.BB  4  3RV1721  50  480 
3RF3405-.BB  4  3RV1721  10  600 
3RF3410-.BB   8  3RV1721  5  600 
3RF3412-.BB   8  3RV1721  5  600 
3RF3416-.BB  8  3RV1721  5  600 
3RF3416-.BB  10  3RV1721  5  600 
 
Table 3- 15  Circuit breaker ratings for solid-state reversing contactors 
  Fuses     
3RF34  Max. size [A]  Type  Current [kA]  Voltage [V] 
3RF3403-.BD  4  3RV1721  50  480 
3RF3405-.BD  5  3RV1721  30  480 
3RF3410-.BD  8  3RV1721  5  480 
 
 
NOTICE 
 
Short-circuit currents 
Short-circuit currents can result in material damage. 
When combining solid-state switching devices and overload relays the device with the 
lowest rated value is decisive as regards short-circuit fuse protection.