SIRIUS 3RA21/22 load feeders   
6.6 Mounting 
  SIRIUS Innovations 
574  System Manual, 01/2011, A8E56203870002-03 
Combination 
Power 
Clearance between feeders 
Permissible installation: h = horizontal, v = vertical 
Max. ambient temperature: 
 
 
 
 Vibration and shock
1)
 
 
A  mm  h, v  ° C   
3RA21 direct-on-line starter, spring-
loaded connection, DIN rail or wall 
 
≤ 14 0 h, v  60 
10 h  60 
S00 
14 … 16
0 h, v  40 
Unlimited 
≤ 29 0 h, v  60 
10 h  60 
S0 
29 … 32
0 h, v  40 
DIN rail adapter required 
3RA21 direct-on-line starter, spring-
loaded connection, busbar 
 
S00  16
2)
 
2)
  Vibration and shock kit 8US19 98-1CA10 
required 
S0  32
2)
 
2)
  Vibration and shock kit 8US19 98-1CA10 
required 
3RA22 reversing starter, spring-loaded 
connection, DIN rail or wall 
 
≤ 14 0 h, v  60 
10 h  60 
S00 
14 … 16
0 h, v  40  
DIN rail adapter required 
≤ 29 0 h, v  60 
10 h  60 
S0 
29 … 32
0 h, v  40 
Unlimited 
3RA22 reversing starter, spring-loaded 
connection, busbar 
 
S00  16
2)
 
2)
  Vibration and shock kit 8US19 98-1CA10 
required 
S0  32
2)
 
2)
  Vibration and shock kit 8US19 98-1CA10 
required 
Motor starter protector and soft starter, 
screw connection, DIN rail or wall 
 
S00  16
2)
 
2)
  The feeder must be screwed tight to the 
top of the motor starter protector with two 
screws and fastened to the bottom of the 
soft starter with a self-locking screw. Not 
approved for railways, power plants, or 
shipbuilding.