COMMANDS
Not
e
If the module is in operating status „Hardware fault“ or operating fault, then only the
instructions (8) LOADDEFAULT VALUES, (1) SERVICE_ON, (2) SERVICE_OFF
and (9) ACK_ERROR, (150, 156) DOSING (FILLING) STOP are accepted, all
other instructions are rejected with a data-/operating error
6.2 Command List
Code Command explanation Comment
Service and adjustment commands
1
Switch on service operation
The SIWAREX must be switched to service
operation to perform the adjustment. A non-adjusted
scale cannot get out of service operation.
No totalizing
2
Switch off service operation
After the adjustment, service operation can be
switched off. Only then can the scale accept
weighing commands.
Service operation
3
Adjustment command zero point valid
The beginning of the characteristic curve - zero point
of the scale - is defined with the momentary dead-
load.
Service operation
4
Adjustment command Adjustment weight 1 valid
The first adjustment weight is assigned with the
momentary weight.
Service operation
5
Adjustment command Adjustment weight 2 valid
The second adjustment weight is assigned with the
momentary weight.
Service operation
6
Adjustment instruction Adjustment weight 3
valid
The third adjustment weight is assigned with the
momentary weight.
Service operation
7
Adjustment instruction Adjustment weight 4
valid
The fourth adjustment weight is assigned with the
momentary weight.
Service operation
8
Predefine all data records with default values
All parameters are set to the status that was
assigned originally by the manufacturer.
Service operation
SIWAREX FTC