Bit No. Name Range of Values / Meaning Reference
26 Status change Status change running. The information is set with the
following events:
- Start-up in volumetric operation
- Setpoint change in volumetric operation
- Switch to grav. operation. For the time of the monitoring
delay (DR 12)
- defined switch to volumetr. operation upon flow rate fault
27 Reserved Reserved
28 Dosing active Switch on material discharge organ
29 Loading active Loading (belt scale) is activated.
30 Loading complete Loading (belt scale) is complete.
31 Reserved Reserved
Table 5-15 DR 30 - Conti-Status flags
5.15.3 DR 30 - Gross Process Value
The cu
rrent gross weight value. Dimension: Weight Unit [WU].
5.15.4 DR 30 - Net Process Value
The cu
rrent net weight value. Dimension: Weight Unit [WU].
5.15.5 DR 30 - Tare Process Value
The cu
rrent tare weight value. Dimension: Weight Unit [WU].
5.15.6 DR 30 - G/N Weight
The momentary weight value whi
ch will be used for the main display. Dimension:
Weight Unit [WU].
5.15.7 DR 30 - G/N Weight_x10
The momentary weight value in increased resolution whi
ch will be used for the
main display. Dimension: Weight Unit [WU].
5.15.8 DR 30 - Tare
Th
e current weight value tare (numeral step from DR 3). Dimension: Weight Unit [WU].
5.15.9 DR 30 – Belt Speed
The cu
rrent belt speed defined in length units (e.g. m) per second.
5.15.10 DR 30 – Belt Speed in % of the Nominal Speed
The cu
rrent belt speed in % of the predefined nominal speed.
5.15.11 DR 30 – Belt Loading in % of the Nominal Load
The cu
rrent belt load is output as the relationship of the current belt load to the
nominal belt load.
5-76 SIWAREX FTC