Loading...
Rated current 0.5 A
Max. output current 0.6 A
max. cumulative current of all outputs 2 A
Isolation 500 V
Voltage drop on assembly < 0.25 V
Switching delay 12 ms
Short-circuit proof Yes
1
1
Pulsed output current upon short-circuit
Table 14-5 Data: Digital inputs, Digital outputs
14.6 Counter Input CI (for belt scale)
Number 1
Rated voltage DC 24 V
Isolation
conforming with IEC 1131, UL 508,
CSA C22.2 NO. 142
500 V
Voltage range for H signal DC 9 V to 30 V
Voltage range for L signal DC -3 V to 5 V
Input current (15 to 30 V) 2 to 15 mA
Switching frequency max. 10 kHz
Isolation
500 V
Table 14-6 Data: Counter input CI
14.7 RS 232C Interface
Baud rate 1200 to 115200 Baud
Data bits 8
Parity Even
Stop bits 1
Max. distance 15 m
Signal level Conforms to EIA-RS232C
Isolation
500 V
Table 14-7 Data: RS 232C interface
14.8 RS 485 Interface
Baud rate
1200 to 19200 Baud
Data bits 7 or 8
Parity even / odd
Stop bits 1 or 2
Max. distance 1000m at 1200 Baud
Signal level Conforms with EIA-RS485
Termination resistance 390 / 220 / 390
Isolation
500 V
Table 14-8 Data: RS 485 interface
14-128 SIWAREX FTC