TECHNICAL DATA
Load cell power Voltage
Current
Typical DC 10.2 V *
184 mA
Permitted load cell resistance without Ex-i-Interface > 56
< 4010
Permitted load cell resistance with Ex-i-Interface > 87
< 4010
Monitor for sensor inputs Typical 5 V
Hysteresis 120 mV
Response time for sensor line monitor 1 s
Common mode rejection CMRR @50 Hz Typical 120 dB
Measuring value filtering for low pass filter 0.05...20 Hz
Measured value filtering for average value filter 2...250 values
Impedance measurement for load cells Measuring range 56 ...4010
Precision ±5%
Repeat accuracy <1 %
Isolation
500 V
* Values apply to module output
Table 14-3 Data: Load Cell Connection
14.4 Analog Output
The defined replacement value is output for active BASP-/OD signal
(S7 CPU).
Range 1 0 to 20 mA
Range 2 4 to 20 mA
Max. total error at 25 °C < 0,5 % *
Refresh rate 10 ms
Load (incl. line resistance) 520 , 30 nF
Cable length 0.5 mm
2
200 m
Temperature coefficient max. ± 75 ppm / K
Resolution 12 Bit (4096 parts) **
Isolation
500 V
* Definitions apply with current >0.5mA
** Resolution reduced by 20 % with operations 4 to 20 mA
Table 14-4 Data: Analog Output
14.5 Digital Inputs (DI), Digital Outputs (DO)
The defined value is always output on the DO for active BASP-/OD
signal (S7 CPU).
An inverse diode (recovery diode) is to be used on the consuming
component with inductive loads on the DO.
DI DO
Number 7 8
Rated voltage DC 24 V
Isolation
500 V
Voltage range for H signal DC 15 V to
30 V
Voltage range for L signal DC -3 V to
5 V
Input current (15 to 30 V) 2 to 15 mA
Switching frequency max. 50 Hz max. 50 Hz
SIWAREX FTC
14-127