MESSAGES AND DIAGNOSIS
Error
No.
Data and op
erating
errors
- Meaning
Explanation
12 Command cannot be
executed because the
previous command is
not finished yet.
A new command cannot interrupt the execution of the current
command. Activate the command after the current command
has finished executing.
13 Command or data
transfer not allowed in
this operating status
A new command cannot be executed in this operating status.
16 Reserved
21 Command not
allowed since the
assembly is damaged
the OD is active
The activated command is not allowed since the scale has a
fault or SIMATIC CPU is in STOP status. Correct the error (red
LED on the front must go off).
22 DI assignment not
allowed
You have assigned the digital inputs incorrectly. Correct your
assignments.
23 DO assignment not
allowed
You have assigned the digital outputs incorrectly. Correct your
assignments. The outputs may only be defined with numbers 0
to 63 and 255.
25 Time range for pulse
input not allowed
The measurement time entry for the pulse input is incorrect.
The permitted range lies between 100 msec and 10000 msec.
Correct the entry.
29 Ext. analog default
value implausible
The current value entry for the analog output lies outside of
the defined (DR 7) range. Enter a smaller value.
30 Analog output
replacement value
implausible.
The replacement value for the analog output lies outside of the
defined (DR 7) range. is too large for the analog output. Enter
a smaller value.
31 Analog zero value to
analogue end value
implausible
The default analog zero value or analogue end value is
incorrect. Change at least one of the values.
35 Baudrate not
permitted for RS232
The baudrate is not permitted for the RS232 interface. Define
the baud rate.
36 Process alarm
assignment or
process value
assignment
implausible
The allocation of the process alarms or process values in DR
7 is incorrect for the S7 interface. Change your assignment.
37 Baud rate not defined
for RS485
The baud rate for the RS485 interface is not defined. Define
the baud rate.
43 Trace task not
possible since MMC
full
44 Trace task cannot be
executed, since MMC
is defective or non-
existent
45 Trace recording cycle
too small
The recording cycle is too small in DR 7. Define a longer
recording cycle (at least 5 x 10 msec. for MMC).
SIWAREX FTC
7-101