No.
Technology message
- Meaning
Explanation
13 Error Output device not ready Logging is not possible because the defined
output device was not ready.
If the printer is defined as the output device,
check whether the printer is connected properly
and if it is ready or not.
If the MMC is selected as the MMC, check for
whether a formatted MMC is inserted.
14
Logging not possible since the weight
lies outside of the weighing range
Logging not possible since the weight lies
outside of the weighing range in verifiable
application (code in DR 3 OIML)
15
Reserved
16
Logging is not possible since there is no
log ID in the print text
Logging is not possible since no log ID is
defined in the log string (verifiable application,
code in DR 3 - OIML).
17
Logging is not possible because the
printer is not ready
Logging is not possible because the printer has
not indicated that it is ready. Check the printer.
18
Logging is not possible because the
MMC is defective or is not inserted
Logging is not possible because the MMC is
defective or it has been removed. Change or
insert the MMC.
19
Logging is not possible because the
SIWATOOL-driver is active
Logging is not possible because the
SIWATOOL program is active on the interface.
Disconnect the connection to the PC and
connect a printer.
20 Reserved
21-40 Error in weighing function
21
Scale command aborted, not at standstill
Taring/Zero definition or logging not possible
because no standstill has been achieved within
the standstill waiting time 1 defined in DR 3.
22
Zero setting not possible
The switch-on weight lies outside of the
value range defined in DR 3 for zero
setting with the maximum positive and
negative weight.
23
Zero setting / taring not possible
Zero definition or zero setting not possible
because the gross is outside the zero definition
range or taring is not possible because the tare
maximum load has been exceeded.
41-100 Error in continuous operation
41 Belt speed too small Belt speed too small. Test the belt.
42 Belt speed too large Belt speed too large. Check the drive control.
43 Belt load too small Belt load too small, check the material feed.
44 Belt load too large Belt load too large, check the material feed.
45 Flowrate too small Flowrate too small, check the material feed.
46 Flowrate too large Flowrate too large, check the material feed.