Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 7 Boiler control 23.04.2009
Number Text (as supplied) Effect
2301
[K1 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
2302
[K2 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
2303
[K3 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
2304
[K4 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
2305
[K5 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
2306
[K6 burner] fault Urgent message; acknowledgement can be
parameterized; factory setting: “Acknowl-
edge“. Boiler stop
Number Text (as supplied) Effect
2311
[K1 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
2312
[K2 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
2313
[K3 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
2314
[K4 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
2315
[K5 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
2316
[K6 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Effect can be parameterized;
factory setting: “Stop“ (boiler stop)
Number Text (as supplied) Effect
2321
[Boiler 1] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2322
[Boiler 2] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2323
[Boiler 3] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Fault burner
Fault burner operation
supervision
Water shortage