Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 7 Boiler control 23.04.2009
Number Text (as supplied) Effect
2324
[Boiler 4] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state Urgent, boiler stop, must be
acknowledged
2325
[Boiler 5] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2326
[Boiler 6] water shortage Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Number Text (as supplied) Effect
2331
[Boiler 1] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2332
[Boiler 2] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2333
[Boiler 3] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2334
[Boiler 4] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2335
[Boiler 5] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2336
[Boiler 6] overpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Number Text (as supplied) Effect
2341
[Boiler 1] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2342
[Boiler 2] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2343
[Boiler 3] underpressure Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Overpressure
Underpressure